Overview:
An issue has been identified in Forcefield 8 when programming an 8 Door TS1066 NAC, where door numbering is currently handled incorrectly. Doors 1-4 are shown as Doors 5-8, and Doors 5-8 are shown as Doors 1-4.
Workaround:
The current workaround for this issue is when using Forcefield to always program or edit Doors 1-4 by editing Doors 5-8, and to program or edit Doors 5-8 by editing Doors 1-4.
Also worth noting is that doors will appear the correct way around if viewing programming in CTPlus. It is only in Forcefield that the door numbers are swapped around.
Extra Information:
Current latest Forcefield version that this issue has been identified in: Forcefield 8.1.0 B32