Converting to software IUM
(Adding memory section in Titan help)
Use the following steps to upgrade a non-IUM Challenger system to use software IUM.
1. Ensure the control panel uses firmware version 8.128 or later. If using 4 Door or Lift controllers ensure they use R-300107 or later. Obtain firmware if needed.
2. Upload the existing control panel’s system into the system management software.
3. Power down the Challenger system.
4. Install firmware version 8.128 or later (unless already installed).
5. Re-set the panel and apply power.
6. Use RAS Install menu option 14 Defaults to program software IUM mode (default option 95).
7. Default any four door controllers (on first start up they will inherit the IUM setting).
8. Connect with the system management software.
9. Download the system back into the panel.
Converting to hardware IUM
Use the following steps to upgrade a non-IUM Challenger system to use hardware IUM.
1. Purchase the required TS0883 or TS0884 hardware IUM modules for the control panel and for all Intelligent 4-Door or 4-Lift DGPs.
2. Upload the existing control panel’s system into the system management software.
3. Power down the Challenger system.
4. Install the IUMs and associated firmware.
5. Re-set the control panel and apply power.
6. Connect with the system management software.
7. Download the system back into the control panel.