Intelligent Controller macro types
EVENT DESCRIPTION
DOOR OPEN Door Open command is active (To unlock / start shunt)
DOOR UNLOCKED Lock Output is active to unlock the door
DOOR OVERRIDE The Over-ride Time zone assigned to the door is valid
* DOOR OVERRIDE INHIBIT The Override Time zone is inhibited
DOOR DISABLED Door is disabled completely. (From keypad or computer)
# DOOR READER DISABLED Reader is disabled
** DOOR DUAL CUSTODY INSIDE Dual Custody access is required at the "IN" Reader
** DOOR DUAL CUSTODY OUTSIDE Dual Custody access is required at the "OUT" Reader
** DOOR LOW SECURITY INSIDE Card & PIN required for access at the "IN" Reader
** DOOR LOW SECURITY OUTSIDE Card & PIN required for access at the "OUT" Reader
** DOOR ANTI PASSBACK Anti Pass back is active
DOOR SHUNTING Shunt timer is running
DOOR SHUNT WARNING Shunt warning timer is running
DOOR AREA SECURE Area assigned to Door is Secure (Output Event will disable
Door if "Access denied in secure")
DOOR INTERLOCK Interlock input/s are unsealed
* DOOR INTERLOCK OVERRIDE If the interlock has been overridden
DOOR KEYPAD DURESS Duress PIN code entered at Door Keypad
DOOR READER FAULT Fault detected on reader (Comms / tamper / etc)
DOOR LOCK FAULT Cable tamper / fault detected on Lock relay wiring
DOOR DOTL Door Contact is unsealed after shunt timer has expired
DOOR FORCED Door Contact is unsealed with no valid door command
DOOR LED LED 1 output is active
DOOR LED 2 LED 2 output is active
DOOR BUZZER BUZZER output is active
DOOR RANDOM BIT An event is generated at random when the door is accessed
DOOR ACCESS DENIED Door access has not been allowed
DOOR ACCESS GRANTED Door access has been allowed
DOOR ACCESS GRANTED TRACED Door access has been granted to a user with trace on
DOOR ACCESS GRANTED 1ST BADGED Door access has been granted when badged once
DOOR ACCESS GRANTED 2ND BADGED Door access has been granted when badged twice
DOOR ACCESS GRANTED 3RD BADGED Door access has been granted when badged three times
DOOR ACCESS GRANTED IN BUTTON Door access has been granted and IN Button pressed
DOOR ACCESS GRANTED OUT BUTTON Door access has been granted and OUT Button pressed
DOOR FIRE OVERRIDE Secondary override is active
DOOR SECURE When the Door is LOCKED and the Door is CLOSED.
AREA ACCESS Area in Access (16 Events - 1 per Area)
AREA ALARM Input/s in Alarm in Area (16 Events - 1 per Area)
AREA ISOLATED Input/s Isolated in Area (16 Events - 1 per Area)
AREA UNSEALED Input/s Unsealed in Area (16 Events - 1 per Area)
* DGP RELAYS System relay assigned to this DGP is active (16 Events - 1 per relay)
RAS OFF-LINE RAS on Controller LAN is Off-line (16 Events - 1 per RAS Address)
DGP OFF-LINE DGP on Controller LAN is Off-line.
INPUTS Input on this DGP unsealed (16 Events - 1 per input)
AUXILLARY 1 INPUT EVENT Special Interface required. (32 events)
AUXILLARY 2 INPUT EVENT Special Interface required. (32 events)
AUXILLARY 3 INPUT EVENT Special Interface required. (32 events)
AUXILLARY 4 INPUT EVENT Special Interface required. (32 events)
REGION LIMIT When the number of people in any region reaches the preset limit
** PHYSICAL RELAYS Relay connected to this DGP is active (255 Events - 1 per relay)
FLOOR ACCESSED Free Access available to floor (64 Events - 1 per floor)
FLOOR CALL BUTTON Floor selection button pressed (64 Events - 1 per floor)
FLOOR DISABLED Floor is disabled from being selected (64 Events - 1 per floor)
FLOOR LANDED Floor where lift car is currently landed (64 Events - 1 per floor)
FLOOR SEND Command to send lift car to floor (64 Events - 1 per floor)
CONTROLLER MAINS FAIL Mains Fail condition exists on the Controller (1 Event)
CONTROLLER LOW BATTERY Low Battery condition exists on the Controller (1 Event)
CONTROLLER BATTERY TEST ACTIVE The Battery Test on this Controller is running (1 Event)
CONTROLLER BATTERY TEST FAIL The Battery Test Failed on this Controller (1 Event)
CONTROLLER FUSE FAIL Fuse Fail condition exists on the Controller (1 Event)
CONTROLLER SIREN FAIL Siren Fail (Siren Tamper) condition exists on this Controller (1 Event)
CONTROLLER SIREN ACTIVE The Siren output (16th relay) is active (1 Event)
CONTROLLER TAMPER Cabinet tamper condition exists on this Controller (1 Event)
CONTROLLER DGP OFF-LINE Controller is not communicating with the Challenger Panel ( 1 Event)
* Denotes rule can only be activated as a result of another Door Macro.
** Denotes rule can only be activated as a result of another Door Macro and the
Function of the door. (The input will always be true if the function is set in the
Programming.
# Users with the 'Privilege' Status override the 'Reader Disabled' function